Requires
Flash Player 9

Version Test
Download Flash

RW newsbytes
Reference Room

Broadcast Law Review
Tech Tips
Guy Wire
IBOC DAB
Product Evaluation
RW Special Report

Skip Pizzi/The Big Picture
Wire for Sound
Workbench
IT Management
Roots of Radio
Spotlight on RF Safety
Radio Road Warrior
Green Radio
Certification Corner
Classifieds

Subscribing to RW
Customer Service


The Leslie Report


Cool Stuff Awards Radio World Announces 2008
“Cool Stuff” Award Recipients


Excellence in Engineering Award

Subscribe to Email Newsletters


Click on the widget below to view the last issue of
Radio World Engineering Extra


Requires
Flash Player 9

Version Test
Download Flash




:: view all articles in:
The Reference Room :: Workbench

UPS & Generator: A Happy Marriage
 
1.03.2007    
John Bisset has worked as a chief engineer and contract engineer for four decades. He is the northeast regional sales manager for Broadcast Electronics and in 2007 received the SBE’s Educator of the Year Award. Reach him at (571) 217-9386 or jbisset@bdcast.com. Faxed submissions can be sent to (603) 472-4944. Submissions for this column are encouraged and qualify for SBE recertification credit.


Photos

(click thumbnail)
Fig. 1: Harry Bingaman used parts from his junk box to make this protective switch cover.


(click thumbnail)
Fig. 2: The cover in place.


(click thumbnail)
Fig. 3: Road Ready Cases offers cooling fans and transport rollers in its line of cases.

Solving a problem gives any engineer a boost. But if we solve it using items from the junk box, well, that really makes our day.

Consider the phasor or pattern controller. It’s not an issue when located at an out-of-the-way transmitter site; but collocate these pushbuttons with a studio and at some point someone’s going to want to experiment.

For sure, mode change may be tied to the remote control. But having selection access for maintenance is helpful. The issue is how to keep curious fingers at bay.

Harry Bingaman, engineering manager for Sunbury Broadcasting, fashioned a removable switch cover, seen in Figs. 1 and 2, using spare parts. The panel can be removed easily for maintenance access, and the cover keeps the switches “out of sight and out of mind.”

* * *

Here’s a neat idea: Combine a heavy-duty road case with built-in electric cooling fans!

California-based Road Ready Cases is where you find “Cool Cases” that bring much-needed relief for remote broadcasters as well as production companies.

The Cool Cases line will cool live gear by an average of 12 degrees F. The company looks for new ways to further the life of customers’ gear; this built-in safeguard, seen in Fig. 3, will guard against overheating. Note the built-in transport rollers. No more hand truck!

The company’s motto is, “Built for the Rigors of the Road.” Give ’em a look if you need a heavy-duty case for your remote or PA equipment.

For information on Road Ready Cases and the company’s product catalog, go to www.roadreadycases.com.



* * *

Ron Schacht works for Three Eagles Communications out of Lincoln, Neb., handling stations in Iowa and Eastern Minnesota. He has suggestions for those who have problems running their UPS from a generator. Ron has encountered this situation several times and so far has found it to be caused by three issues.

First, and most common, is the generator output frequency. Since just about all UPS systems use ferroresonant transformers, they won’t accept 57 or 63 Hz. They need exactly 60 Hz to tell the rest of the UPS that the world is fine.

So how do you tell what your generator is generating? You can use a small filament transformer on the generator to drive a frequency counter or oscilloscope to get the generator governor to run at whatever speed is necessary to produce 60 Hz. The governor should hold the frequency to 60 Hz, regardless of the load.

You can usually locate the governor easily; it is linked to the carburetor throttle plate and has a big spring on it with an adjusting screw. Too many times people adjust these for voltage and not frequency.

The second issue is generator voltage. It should be within the tolerance of the UPS, say 110 to 130 volts. This is adjusted in the newer generators by a pot in the electronic field regulator circuit. Older generators have what looks like a multi-pole relay with a large coil. Each contact has a slightly different spring tension; as contacts pull in and drop out depending on voltage, different resistances are inserted in the field winding to adjust output voltage. Although these are trickier to adjust, you can set them, with patience. Just make sure you are operating with normal load when you do the tinkering.

The third situation Ron has encountered is with cheaper generator sets. On these temporary contractor-type generators, you may find spikes on the output waveform, caused by the output voltage regulators using SCRs.

Look at the output of the gen set. You may see big spikes on the sine wave. Ron has had luck sticking a couple of MFDs (microFarads) of AC motor starting capacitors across the output. Although it upsets the power factor in a positive way, and reduces the output capacity of the generator somewhat, it will smooth out the waveform enough to let the UPS run fine. Just make sure that the capacitors you use are the AC motor type; generally about 10 uF is enough. Ron has used motor caps for split phase motors rated at 330vac too.

These are not the only reasons a UPS won’t run on a generator, but they’re the ones Ron has encountered in the prairies of the upper Midwest.



Sponsored Links
Transradio: DRM, AM, VHF/FM - We make the transmitters. Visit us now at www.transradio.de for more information.
Harris Corporation's Broadcast Communications Division designs products that streamline workflow of content production, processing, transmission, management, storage, test and measurement and broadcast graphics. Click here!
MultiDyne provides a wide array of video and fiber optic transport solutions, each with the highest image quality in the industry. Click here!
Nucomm delivers industry-leading microwave solutions for high-data-rate HD and IP File transport applications from portable ENG/OB to rack-mounted fixed link systems. Click here!
RF Central - Total RF solutions manufacturer (TV broadcast): Full-Service 2GHz Relocation, COFDM, HDTV ENG components, complete links.


advertisement

McGrawHill Construction: Online at Sweets.com
Research Construction Products and manufacturers in a library of more than 1,800 building product catalogs. Visit us today!

Krohn-Hite Corporation: Company Information
Offers a full line of calibrator products including AC and DC calibrators, simulators, secondary standards, low noise power sources and more.




 
Radio World CoolCasts

Take a virtual booth tour of the products that won the 2008 Radio World "Cool Stuff" Award.
Radio World’s 2008 Source Book & Directory... ...is now available in a special digital edition. In response to many reader requests, our handy annual resource is now online for free. (A 12 MEG PDF)
back   Home | Subscribe | About NewBay Media | Contact Us